SDV6 medium-voltage outdoor vacuum distribution circuit breakers (15.5 kV - 38 kV)
As of October 1, 2008, our U.S. business is called Siemens Energy, Inc.
- SDV6 medium-voltage outdoor vacuum distribution circuit breaker (15.5 kV - 38 kV) overview
SDV6 medium-voltage outdoor vacuum distribution circuit breaker (15.5 kV - 38 kV) description and features
Siemens SDV6 medium-voltage outdoor vacuum circuit breakers are available in voltage ratings from 15.5 kV to 38 kV. Siemens technology is proven in thousands of installations around the world. Add a Siemens protective relay to match any typical application and have a complete packaged solution.
15.5 kV, 20 kA to 40 kA, 1200 A to 3000 A, 110 kV BIL
27.6 kV, 20 kA to 25 kA, 1200 A to 2000 A, 150 kV BIL
38.0 kV, 20 kA to 40 kA, 1200 A to 2000 A, 200 kV BIL
Reliable performance - time proven operating mechanism
3AH3 operator derived from operators introduced in 1977
Common operator for all ratings
Extended capacitor switching (optional)
Out-of-phase switching ratings (optional)
Large control compartment
Porcelain dry-type bushings
Robust design
Stainless steel exterior hardware
Highly reliable vacuum interrupters - MTTF over 43,000 years
Pair with Siemens protective relays to match any typical application
Moderate and high seismic qualification (Zones 1-4)
Meets or exceeds the latest ANSI, IEEE and NEMA standards
ANSI "rain tested" enclosure (C37.20.2 1999)
Circuit breakers shipped completely assembled and ready to install
SDV6 technical data
Circuit breaker type | Rated maximum voltage | Rated withstand voltages | Rated withstand voltages | Rated short-circuit and short-time current | Rated interrupting time1 |
| | Lightning impulse (BIL) | Power frequency | | |
| kV, rms | kV4 | Hz | kA, rms | ms / cycles |
15.5-20 | 15.5 | 110 / 142 | 50 | 20 | 83 / 5 |
15.5-25 | 15.5 | 110 / 142 | 50 | 25 | 83 / 5 |
15.5-31.5 | 15.5 | 110 / 142 | 50 | 31.5 | 83 / 5 |
15.5-40 | 15.5 | 110 / 142 | 50 | 40 | 83 / 5 |
27.6-20 | 27.6 | 150 / 194 | 60 | 20 | 83 / 5 |
27.6-25 | 27.6 | 150 / 194 | 60 | 25 | 83 / 5 |
38.0-20 | 38.0 | 200 / 258 | 80 | 20 | 83 / 5 |
38.0-25 | 38.0 | 200 / 258 | 80 | 25 | 83 / 5 |
38.0-31.5 | 38.0 | 200 / 258 | 80 | 31.5 | 83 / 5 |
38.0-40 | 38.0 | 200 / 258 | 80 | 40 | 83 / 5 |
Circuit breaker type | Rated continuous current | Rated transient recovery voltage (TRV)2 | Rated transient recovery voltage(TRV)2 | Rated permissible tripping delay time | Rated closing and latching current |
| | uc TRV peak value | t3 time to voltage uc | Y | |
| A, rms | kV | us | sec | kA, peak |
15.5-20 | 1200, 2000 | 29.2 | 32 | 2 | 52 |
15.5-25 | 1200, 2000 | 29.2 | 32 | 2 | 65 |
15.5-31.5 | 1200, 2000, 3000 | 29.2 | 32 | 2 | 82 |
15.5-40 | 1200, 2000, 3000 | 29.2 | 32 | 2 | 104 |
27.6-20 | 1200, 2000 | 52.1 | 45 | 2 | 52 |
27.6-25 | 1200, 2000 | 52.1 | 45 | 2 | 65 |
38.0-20 | 1200, 2000 | 71.7 | 59 | 2 | 52 |
38.0-25 | 1200, 2000 | 71.7 | 59 | 2 | 65 |
38.0-31.5 | 1200, 2000 | 71.7 | 59 | 2 | 82 |
38.0-40 | 1200, 2000 | 71.7 | 59 | 2 | 104 |
Control voltages, IEEE C37.06
Nominal | Range close | Range trip | Close coil A | Trip coil3 A | Spring charging motor A run (average) | Spring charging motor charging seconds |
48 Vdc | 36 - 56 | 28 - 56 | 2.1 | 11.4 / 30 | 8 | 10 |
125 Vdc | 90 - 140 | 70 - 140 | 1.0 | 5.4 / 7.4 | 4 | 10 |
250 Vdc | 180 - 280 | 140 - 280 | 0.5 | 2.1 / 4.2 | 2 | 10 |
120 Vac | 104 - 127 | 104 - 127 | 0.9 | ---- | 6 | 10 |
240 Vac | 208 - 254 | 208 - 254 | 0.4 | ---- | 3 | 10 |
1 Optional 50 ms (three-cycles) with 48 Vdc, 125 Vdc or 250 Vdc trip voltage.
2 TRV values are in accord with IEEE C37.06-2009 TRV peak value uc is roughly equal to historic E2 value in IEEE C37.06-2000. Value t3, time to voltage uc is approximately 1/1.138 times the T2 value in IEEE C37.06-2000.
3 First value is for standard 83 ms / five-cycle interrupting time. Second value is for optional 50 ms / three-cycle interrupting time.
4 First value is full-wave impulse withstand with circuit breaker open or closed. Second value is chopped-wave impulse withstand, applicable only with circuit breaker closed.
SDV6 dimensions in inches
Rating | A | B | C | D | E | F | G (Minimum) | G (Maximum) | H | I | J |
15.5 kV up to 2000 A | 10.8 | 13.0 | 51.0 | 58.5 | 28.2 | 15.9 | 105.8 | 129.4 | 44.1 | 39.9 | 44.0 |
15.5 kV 3000 A | 12.2 | 15.7 | 59.3 | 63.7 | 28.2 | 21.3 | 105.8 | 129.4 | 44.1 | 39.9 | 52.3 |
All 27.6 kV | 12.2 | 15.7 | 59.3 | 58.5 | 28.2 | 15.9 | 106.3 | 129.9 | 44.1 | 39.9 | 52.3 |
All 38 kV | 17.7 | 19.7 | 75.2 | 78.5 | 45.2 | 24.3 | 122.0 | 145.6 | 71.5 | 63.5 | 67.2 |
15.5 kV and 27.6 kV SDV6
SDV6 front, side and rear view photos