Type GM38 metal-clad air-insulated switchgear can meet almost any switchgear application from 23 kV through 38 kV. The horizontal drawout vacuum circuit breakers occupy the lower cell with voltage transformers (VTs) or drawout fuses available in the upper cell. The lower cell may be used for auxiliaries, such as VTs, a control power transformer (CPT) or drawout fuses. Two types of outdoor housing are offered: non-walk-in and shelter-clad.
| Measured parameter | Units | Circuit breaker type 38-3AH3-1500 [1] | Circuit breaker type 38-3AH3-31 [2] | Circuit breaker type 38-3AH3-40 [2] | ||
| General | Nominal voltage class | kV | 38.0 | 38.0 | 38.0 | |
| General | Nominal three-phase MVA class | MVA | 1,500 | ---- | ---- | |
| Rated values | Rated voltage | Maximum design voltage (V) | kV rms | 38.0 | 38.0 | 38.0 |
| Rated values | Rated voltage | Voltage range factor (K) | ---- | 1.65 | 1.0 | 1.0 |
| Rated values | Insulation levels | Withstand voltage levels power frequency | kV rms | 80 | 80 | 80 |
| Rated values | Insulation levels | Withstand voltage levels lightning impulse (BIL) | kV peak | 150 | 150 | 150 |
| Rated values | Rated current | Continuous | A rms | 1,200, 2,000, 3,000FC [3] | 1,200, 2,000, 3,000FC [3] | 1,200, 2,000, 3,000FC [3] |
| Rated values | Rated current | Short-circuit (at rated maximum design voltage) (I) | kA rms sym | 21 | 31.5 | 40 |
| Rated values | Rated current | Interrupting time | Cycles / ms | 5 / 83 [8] | 5 / 83 [8] | 5 / 83 [8] |
| Rated values | Rated current | Permissible tripping delay (Y) | Sec | 2 | 2 | 2 |
| Related required capabilities | Current | Rated maximum design voltage (V) divided by K = (V/K) | kA rms | 23.0 | 38.0 | 38.0 |
| Related required capabilities | Current | Maximum symmetrical (sym)interrupting (K X I) | kA rms sym | 35 | 31.5 | 31.5 |
| Related required capabilities | Current | Short-time current (K x I) (three seconds) | kA rms sym | 35 | 31.5 | 40 |
| Related required capabilities | Closing and latching(momentary) | Asymmetrical | kA rms | 56 [4] | 50 [6] | 62 [6] |
| Related required capabilities | Closing and latching(momentary) | Peak | kA peak | 95 [5] | 85 [7] | 104 [7] |
[1] Historic constant MVA class (ANSI C37.07-1987)
[2] New constant kA class (ANSI C37.06-2000)
[3] Fan-cooled
[4] 1.6 x K x I
[5] 2.7 x K x I
[6] 1.55 x I
[7] 2.60 x I
[8] Three-cycle (50 ms) interrupting optional.
| Type | Weight lbs. (kg) | Width (W) | Height (H) | Depth (D) | Drawout aisle (DA) |
| Indoor | 5,000 (2,273) | 48.0 (1,219) | 110.0 (2,794) | 130.0 (3,302) | 96.0 (2,438) recommended |
| Outdoor shelter-clad single-aisle | 6,400 (2,909) | 48.0 (1,219) | 132.5 (3,366) | 234.5 (5,956) | 96.0 (2,438) included |
| Outdoor non-walk-in | 5,800 (2,636) | 48.0 (1,219) | 132.5 (3,366) | 139.4 (3,539) | 96.0 (2,438) recommended |
| Continuous current | 38-3AH3-1500 | 38-3AH3-31.5 | 38-3AH3-40 |
| 1,200 A | 800 (363) | 800 (363) | 825 (375) |
| 2,000 A | 900 (408) | 900 (408) | 925 (420) |
| 3,000 A | 1,000 (454) | 1,000 (454) | 1,025 (465) |